Polycab 50 mm LHSFT MMS Conduit Pipe – Medium Mechanical Stress, 3 m Length, CPI0450002
50 mm outside diameter LHSFT series conduit, medium mechanical stress class, IS 9537 Part 3: minimum inside diameter 44.3 mm, 3 m lengths, 15 per pack. Price on request.
Request price
Polycab 50 mm LHSFT MMS Conduit Pipe (code CPI0450002) is a rigid conduit of the medium mechanical stress class from Polycab's LHSFT series to IS 9537 (Part 3): 50 mm outside diameter (tolerance -0.5 mm), at least 44.3 mm inside diameter, supplied in 3 m lengths packed 15 to a standard pack. The 50 mm size is the largest size in the range - for mains, risers, feeder cables and many circuits in one run; the medium class is meant for conduit concealed in brick and block walls and in ceilings - the class most often specified for concealed wiring in homes, flats, offices and shops.
Polycab India Limited is India's largest manufacturer of wires and cables, with 27 manufacturing facilities, 4,300+ authorised distributors, 2,00,000+ retailers and an export presence in 84 countries (polycab.com, October 2026). Polycab is ISO 9001:2015 certified and makes its conduits to IS 9537 (Part 3) and its conduit fittings to IS 3419. Jai Enterprises supplies Polycab 50 mm LHSFT MMS conduit from Bhilai and Raipur all over Chhattisgarh - Bhilai, Raipur, Durg, Korba, Bilaspur, Raigarh, Jagdalpur, Kanker, Ambikapur and every other district - and across India; price on request.
Is this the right one for you?
Check these five things before you order:
- The wires fit the bore: at least 44.3 mm inside diameter - check the number and size of wires against the conduit-capacity table you work to.
- The conduit is concealed in walls or ceilings - the medium mechanical stress class is the usual choice for that.
- Your drawings or tender name Polycab's LHSFT series (codes CPI0420002 to CPI0450002).
- In 50 mm Polycab lists couplers and long slip bends.
- If the size does not fit: for fewer or smaller wires, 40 mm.
At a glance
- Price: on request - call +91 9340081159
- Product: Polycab 50 mm LHSFT MMS Conduit Pipe
- Product code: CPI0450002
- Outside diameter: 50 mm (tolerance -0.5 mm)
- Minimum inside diameter: 44.3 mm
- Mechanical stress class: Medium Mechanical Stress (IS 9537 Part 3)
- Series: LHSFT (Polycab designation; ask for the series data sheet for fire-performance details)
- Length: 3 m
- Standard pack: 15 x 3 m (45 m)
- Colours: black, ivory, grey and red in the Polycab colour chart (availability by size and series on enquiry)
- Standard: IS 9537 (Part 3)
Specifications
- Nominal size: 50 mm (outside diameter)
- Tolerance on outside diameter: -0.5 mm
- Minimum inside diameter: 44.3 mm (medium class, IS 9537 Part 3 value printed in the Polycab catalogue)
- Minimum inside diameter of the three classes at 50 mm: light 45.1 mm; medium 44.3 mm; heavy 43.2 mm
- Length: 3 m per length
- Standard pack: 15 x 3 m (45 m)
- Product code: CPI0450002
- Material: rigid conduit, Polycab LHSFT series (listed in Polycab's uPVC conduits range)
- Standard: IS 9537 (Part 3); fittings to IS 3419
- Colours: black, ivory, grey and red in the Polycab colour chart (availability by size and series on enquiry)
Why choose Polycab LHSFT MMS Conduit Pipe
- LHSFT series - listed by Polycab next to its FRLS series, in the medium and heavy classes; we can obtain the series data sheet for your consultant
- Medium Mechanical Stress class to IS 9537 (Part 3) - a thicker wall than the light class, for conduit concealed in brick and block walls and in ceilings
- Same outside diameters as the FRLS series - so the same Polycab couplers, bends and boxes suit it
- Five sizes, 20 to 50 mm outside diameter - one series for lighting, power, sub-mains and risers
- 3 m lengths in standard packs - 75 lengths of 20 mm down to 15 lengths of 50 mm per pack, easy to count and order
- Matching Polycab fittings to IS 3419 - circular and deep boxes, fan boxes, bends, tees, elbows, couplers, reducers and saddles
Using 50 mm conduit
Wires per conduit: a 50 mm conduit of the medium class has at least 44.3 mm of clear bore. Work out how many wires it can take from the conduit-capacity table you follow (for example the one in IS 732) or the consultant's drawings, and step up a size for long runs with several bends.
Joining and bending: join lengths with a Polycab 50 mm coupler (PVC solvent cement makes the joint permanent in concealed work); use Polycab long slip bends for 50 mm, or a bending spring of the right size.
Fixing: fix surface runs with saddles at regular spacing; in slabs, tie the conduit to the reinforcement and seal open ends before the concrete is poured; leave a draw wire in long runs.
Where it is used
- The largest size in the range - for mains, risers, feeder cables and many circuits in one run
- Concealed wiring in brick and block walls in homes and flats
- Ceiling and wall runs in offices, shops, hotels and schools
- Projects whose drawings or tender name the Polycab LHSFT series
Other sizes of Polycab LHSFT MMS Conduit Pipe
The Polycab LHSFT MMS Conduit Pipe overview page compares all 5 side by side.
- Polycab LHSFT MMS Conduit Pipe 20 mm - code CPI0420002, minimum inside diameter 16.9 mm, pack 75 x 3 m (225 m)
- Polycab LHSFT MMS Conduit Pipe 25 mm - code CPI0425002, minimum inside diameter 21.4 mm, pack 50 x 3 m (150 m)
- Polycab LHSFT MMS Conduit Pipe 32 mm - code CPI0432002, minimum inside diameter 27.8 mm, pack 25 x 3 m (75 m)
- Polycab LHSFT MMS Conduit Pipe 40 mm - code CPI0440002, minimum inside diameter 35.4 mm, pack 25 x 3 m (75 m)
- Polycab LHSFT MMS Conduit Pipe 50 mm (this page) - code CPI0450002, minimum inside diameter 44.3 mm, pack 15 x 3 m (45 m)
Related products
- Polycab LMS FRLS uPVC Conduit Pipe 50 mm - light mechanical stress, minimum inside diameter 45.1 mm, code CPI0150001
- Polycab MMS FRLS uPVC Conduit Pipe 50 mm - medium mechanical stress, minimum inside diameter 44.3 mm, code CPI0250001
- Polycab HMS FRLS uPVC Conduit Pipe 50 mm - heavy mechanical stress, minimum inside diameter 43.2 mm, code CPI0350001
- Polycab LHSFT HMS Conduit Pipe 50 mm - heavy mechanical stress, minimum inside diameter 43.2 mm, code CPI0750002
- Matching 50 mm fittings: Polycab PVC Conduit Coupler, Polycab PVC Slip Type Bend Long
- All uPVC conduits and all conduit fittings
Frequently asked questions
What is the inside diameter of Polycab 50 mm LHSFT MMS conduit?
At least 44.3 mm - the IS 9537 Part 3 minimum for the medium class at 50 mm outside diameter (tolerance -0.5 mm), as printed in the Polycab catalogue. At 50 mm the three classes have a minimum bore of 45.1 mm (light), 44.3 mm (medium) and 43.2 mm (heavy).
How many lengths are in a pack of Polycab 50 mm LHSFT MMS conduit?
15 lengths of 3 m - 45 m per standard pack. Tell us the number of lengths or packs you need.
What is the product code of Polycab 50 mm LHSFT MMS conduit?
CPI0450002. Quote it on your purchase order or tender so the right series, class and size are supplied.
When is 50 mm conduit needed?
For mains and feeder cables, risers and runs that carry many circuits - it is the largest size in the Polycab range. Polycab lists couplers and long slip bends in 50 mm.
LMS, MMS or HMS - which class should I choose?
Light (LMS) for surface runs and above false ceilings, medium (MMS) for conduit concealed in walls and ceilings, heavy (HMS) for slabs, floors and places where the conduit can be crushed or knocked. At 50 mm the minimum bore is 45.1 mm (light), 44.3 mm (medium) and 43.2 mm (heavy).
Where can I buy Polycab 50 mm LHSFT MMS conduit in Chhattisgarh?
From Jai Enterprises, Bhilai and Raipur, which supplies Polycab conduits and fittings across Chhattisgarh - Korba, Bilaspur, Raigarh, Jagdalpur, Kanker, Ambikapur and every other district - and across India. Call +91 9340081159 with the size, quantity and delivery location and we will confirm the price, availability and lead time.
How to order
Supplied by Jai Enterprises, Bhilai and Raipur, to every district of Chhattisgarh and across India. To request a price for Polycab 50 mm LHSFT MMS conduit (CPI0450002), call +91 9340081159 or send an enquiry from this page with the size, the quantity (lengths or packs) and the delivery location, and we will confirm the price, stock and lead time.
Applications
Availability: Enquiry-based — contact us for stock and lead time.